Single-Phase vs Two-Phase Immersion Cooling
How the two immersion cooling principles work, which fluids they need, and what decides between them.
Updated 9 November 2026 · Published by IsoTec
Short answer
In single-phase immersion cooling, the fluid stays liquid. It absorbs heat from the components and is pumped through a heat exchanger. In two-phase immersion cooling, the fluid boils on hot surfaces; the vapour condenses on a cooled coil above the bath and drips back. Single-phase systems use hydrocarbons or esters, two-phase systems mostly fluorinated fluids.
How single-phase immersion works
Servers stand vertically in a tank or sit in closed chassis filled with fluid. A pump circulates the fluid through a heat exchanger – often in a coolant distribution unit (CDU) – where the heat passes to a water circuit. Some designs rely partly on natural convection. Heat is transferred as sensible heat: the fluid warms up as it flows past the components.
Fluids: synthetic hydrocarbons (PAO, GTL), synthetic esters and natural esters. They have high boiling points and low vapour pressure, so tanks can operate at atmospheric pressure with a lid.
How two-phase immersion works
The fluid has a low boiling point, typically around 50 to 60 °C. It boils directly on the hot surfaces of processors and accelerators. Evaporation absorbs a large amount of heat (latent heat) at an almost constant temperature. The vapour rises, condenses on a water-cooled coil and returns to the bath. Tanks must be well sealed to keep vapour losses low.
Fluids: mostly fluorinated (fluorocarbons, hydrofluoroethers, fluoroketones). Most of them fall under PFAS definitions.
Comparison
| Single-phase | Two-phase | |
|---|---|---|
| Heat transfer | Sensible heat, pumped or natural convection | Boiling and condensation (latent heat) |
| Typical fluids | PAO, GTL, synthetic and natural esters | Fluorinated fluids |
| Tank | Covered open bath or closed chassis, atmospheric pressure | Sealed tank with vapour management |
| Fluid losses | Low – the fluid does not evaporate noticeably | Vapour losses must be controlled |
| Fluid cost | Moderate | High |
| Fire behaviour | Combustible – flash point is decisive | Usually non-flammable |
| Regulation | Hydrocarbons and esters are not PFAS | Most fluids are PFAS – EU restriction in preparation |
| Maintenance | Filtration, monitoring of water and acidity | Vapour containment, monitoring of fluid losses and purity |
What decides between them?
- Heat flux: two-phase systems handle very high local heat flux. Single-phase systems reach high rack densities with good flow design and suitable heat sinks.
- Total cost: fluid price, fluid losses and tank complexity favour single-phase systems in most projects.
- Regulatory risk: the planned EU PFAS restriction and 3M’s exit from PFAS production affect the supply of two-phase fluids. See PFAS and immersion cooling.
- Service: single-phase tanks can be opened for maintenance without vapour handling; servers are lifted out and drip off.
Which fluid for single-phase systems?
For single-phase systems the choice is between hydrocarbons and esters. Esters have higher flash and fire points at comparable viscosity, tolerate more moisture and typically transfer heat better; hydrocarbons have lower permittivity. See immersion cooling fluids compared and the data center immersion cooling guide.
Frequently asked questions
Is single-phase or two-phase immersion cooling more common?
Most immersion deployments use single-phase systems because they are simpler, use lower-cost fluids and do not depend on fluorinated fluids.
What is the boiling point of two-phase immersion fluids?
Typically around 50 to 60 °C, so that the fluid boils on the hot components at atmospheric pressure.
Can esters be used for two-phase immersion?
No. Esters have high boiling points and are used in single-phase systems.
Related articles
- Immersion Cooling Fluids for Data Centers
- Immersion Cooling Fluids Compared
- PFAS and Immersion Cooling
- Natural vs Synthetic Esters for Immersion Cooling
Sources and further reading
Choosing a single-phase fluid?
We help you compare ester fluids for your tank design and test them with your components. IsoTec products are supplied to customers outside Germany.