Immersion Cooling Glossary
The key terms of data center immersion cooling and dielectric fluids – short and precise.
Updated 9 November 2026 · Published by IsoTec
Terms A–Z
- Acid number (acidity)
- Amount of potassium hydroxide needed to neutralise the acids in 1 g of fluid, in mg KOH/g. Rises with oxidation and hydrolysis.
- Auto-ignition temperature
- Temperature at which a fluid ignites in air without an ignition source. OCP Rev. 2.0 minimum: 250 °C.
- Breakdown voltage (dielectric strength)
- Voltage at which a fluid between two electrodes fails electrically. OCP lifetime minimum: 6 kV at 1 mm gap.
- CDU (coolant distribution unit)
- Unit with pumps, heat exchanger and controls that circulates the fluid and transfers heat to the facility water circuit.
- Chassis-level (precision) immersion
- Design in which each server sits in its own closed enclosure filled with fluid.
- Cold plate
- Metal plate with internal channels mounted on a processor; used in direct-to-chip cooling.
- Dielectric fluid
- Electrically insulating liquid that can be in direct contact with live electronic components.
- Direct-to-chip cooling
- Liquid cooling in which a coolant flows through cold plates on the hottest components only; the rest is air-cooled.
- ERF (energy reuse factor)
- Share of the energy of a data center that is reused, for example as heat. Reported under EU rules.
- Fire point
- Lowest temperature at which a fluid keeps burning for at least 5 seconds after ignition.
- Flash point
- Lowest temperature at which the vapours of a fluid ignite briefly. OCP Rev. 2.0 minimum: 150 °C (open cup).
- Fluorinated fluid
- Fluid based on fluorocarbons, hydrofluoroethers or fluoroketones; used mainly in two-phase immersion; most are PFAS.
- GTL fluid
- Synthetic hydrocarbon made from natural gas (gas-to-liquids).
- Heat soak test
- Compatibility test in which components are kept in the fluid at elevated temperature – OCP: 80 °C for 14 days for single-phase fluids.
- Hydrolysis
- Reaction of an ester with water that forms acids and alcohols; accelerated by heat.
- Immersion cooling
- Cooling method in which IT hardware is submerged in a dielectric fluid.
- Interfacial tension
- Tension between oil and water; drops when polar contaminants or ageing products are present.
- K-class
- Insulating liquid with a fire point above 300 °C according to IEC 61039.
- Kinematic viscosity
- Resistance of a fluid to flow, in mm²/s. Lower viscosity improves heat transfer and reduces pump power.
- Loss tangent
- Measure of dielectric losses at a given frequency; relevant for high-speed signals in immersion.
- Natural ester
- Dielectric fluid based on refined vegetable oils (triglycerides).
- OCP (Open Compute Project)
- Industry organisation that publishes open specifications, including the Immersion Requirements for fluids and systems.
- Open bath
- Immersion tank at atmospheric pressure, closed by a lid, in which servers stand vertically.
- Oxidation stability
- Resistance of a fluid to reaction with oxygen; tested e.g. according to IEC 61125.
- PAO (polyalphaolefin)
- Synthetic hydrocarbon used as base fluid for single-phase immersion.
- Particle count
- Number and size of particles in a fluid, reported as a code according to ISO 4406.
- Permittivity (dielectric constant)
- Ability of a material to store electrical energy in a field. About 2 for hydrocarbons and about 3 for esters.
- PFAS
- Per- and polyfluoroalkyl substances; very persistent fluorinated chemicals. An EU restriction is in preparation.
- Plasticiser leaching
- Migration of plasticisers from PVC and other plastics into the fluid; makes the plastic brittle and contaminates the fluid.
- Polyol ester
- Synthetic ester made from a polyol and fatty acids; the most common type of synthetic dielectric ester.
- Pour point
- Lowest temperature at which a fluid still flows.
- PUE (power usage effectiveness)
- Ratio of total data center energy to IT energy. A value closer to 1 means less overhead.
- Readily biodegradable
- Result of an OECD 301 test showing fast degradation under test conditions. Does not mean that a substance is harmless.
- Resistivity
- Electrical resistance of a fluid volume, in GΩ·m. OCP: at least 2.00 GΩ·m unused and 0.20 GΩ·m over the lifetime.
- Single-phase immersion
- Immersion cooling in which the fluid stays liquid and is circulated through a heat exchanger.
- Synthetic ester
- Dielectric fluid made by synthesis, mostly a polyol ester; high oxidation stability.
- Thermal interface material (TIM)
- Material between chip and heat sink. Greases can wash out in immersion; solid TIMs are used instead.
- Two-phase immersion
- Immersion cooling in which a low-boiling fluid evaporates on hot components and condenses on a cooled coil.
- Water content
- Dissolved water in a fluid, in mg/kg (ppm), measured by Karl Fischer titration.
- WUE (water usage effectiveness)
- Water use of a data center per unit of IT energy, in litres per kWh.