Material Compatibility in Immersion-Cooled Servers

In immersion cooling, the fluid touches every material in the server for years. A component checklist and the test procedure described by OCP.

Updated 9 November 2026 · Published by IsoTec

Why compatibility decides success

Compatibility works in two directions. The fluid can attack materials: elastomers swell or shrink, plastics soften or become brittle, adhesives let go. And materials can contaminate the fluid: plasticisers, dyes, adhesive components or flux residues dissolve, change the colour and can lower resistivity and dielectric strength. Both effects build up slowly and are often noticed only after months.

Component checklist

ComponentTypical riskWhat helps
Cable assemblies with PVC sheathsPlasticisers leach out; sheath becomes stiff, brittle and cracks; fluid is contaminatedSheaths of PUR or fluoropolymers; test the actual cables
Thermal paste and greases (TIM)Grease matrix dissolves or washes out; chip temperature risesSolid TIMs such as graphite pads or indium foil
Seals, gaskets, EMI foamsSwelling or shrinkage, loss of sealingFKM or PTFE often robust; EPDM, natural rubber and some silicone and NBR grades tend to swell – test
Electrolytic capacitors, coin cellsSwelling of sealsCheck seal material with the component maker
Labels, tapes, adhesives, inksLabels peel off and sink; inks dissolveImmersion-rated labels, acrylate adhesives, laser marking
Optical transceivers and fibresFluid in the optical path, signal lossImmersion-qualified optics
Connectors, sockets, plastic partsDimensional change, contact resistanceLow-level contact resistance tests after soak
Conformal coatings, flux residuesDissolution, fluid contaminationClean assemblies; test coated boards
Hard disk drivesNon-sealed drives failSSDs or hermetically sealed drives
FansDrag in the fluid, wasted powerRemove or switch off

What is different with esters?

Esters are more polar than hydrocarbons. This gives them good solvency and high moisture tolerance, but it also means they can extract plasticisers and interact with some plastics and elastomers differently from hydrocarbons. Fluoroelastomers (FKM) and PTFE generally perform well; for nitrile rubber (NBR) the result depends on the grade. Results from hydrocarbon fluids cannot simply be transferred to esters – the test has to be done with the actual fluid.

How compatibility is tested

The OCP guideline Server Component Immersion Material Compatibility Testing (v1.5, June 2026) describes the procedure for single-phase fluids:

  • Heat soak at 80 °C ± 2 °C for 14 days in a closed vessel, sample fully immersed, at least about 0.8 L of fluid
  • Several replicates to show the spread of results
  • Material checks: visual inspection with photos, change in mass, volume, dimensions and hardness (Shore), functional tests such as contact resistance, dielectric withstand voltage, signal integrity and optical performance
  • Fluid checks: appearance, colour, turbidity and sediment before and after; screening for contaminants such as plasticisers, metal ions, water and organic acids
  • Pass/fail: the fluid must still meet the OCP Immersion Requirements after the soak

The guideline sets no acceptance limits and does not predict service life. Longer tests and a trial in a real tank add certainty.

Practical tips

  • Test the exact part numbers of the bill of materials – the same component from two suppliers can behave differently.
  • Run a blank sample of the fluid without components as reference.
  • Include worst-case parts: cables, labels, gaskets and thermal materials.
  • Re-test when the hardware generation or the fluid changes.

Compatibility testing at IsoTec

We soak your components in our ester fluids, document the changes to the materials and analyse the fluid before and after. You receive a test report as a basis for your qualification. See the qualification checklist and the data center immersion cooling guide.

Frequently asked questions

Can PVC cables be used in immersion cooling?

Often not long-term: plasticisers can leach out of PVC sheaths, which makes them brittle and contaminates the fluid. PUR or fluoropolymer sheaths are commonly used instead. Test the specific cable.

Does thermal paste work in immersion cooling?

Many greases wash out over time. Solid thermal interface materials such as graphite pads or indium foil are used instead.

How long does a compatibility test take?

The OCP guideline describes a 14-day soak at 80 °C for single-phase fluids, plus time for measurements before and after.

Test your components in our ester fluids

Send us your bill of materials and samples – we run the soak tests and report the results. IsoTec products are supplied to customers outside Germany.