Residual Fire Risks of Ester-Filled Transformers – a Risk Register for Fire Engineers
K-class ester fluids remove much of the pool-fire risk of mineral oil. They do not remove every fire scenario. This register lists what remains, why it remains and how it is controlled.
Updated 12 November 2026 · Published by IsoTec
Short answer
Replacing mineral oil with a K-class ester makes it much less likely that released liquid is ignited by a small source or keeps burning as a pool. What remains are mainly scenarios with a strong, persistent ignition source – a high-energy arc during a tank rupture, a long external fire – and components that bring their own fuel, such as bushings with mineral oil. Smoke, spills and firewater also remain to be managed.
Risk register
| Scenario | Typical cause | Effect of K-class fluid | Residual risk | Main controls |
|---|---|---|---|---|
| Internal arc, tank rupture | Insulation breakdown, flashover in a bushing turret | Released liquid is unlikely to keep burning once the arc is cleared | Spray or mist may ignite while the arc persists; pressure wave; liquid release | Fast protection, pressure relief, sudden pressure relay, tank strength, containment |
| Bushing failure | Ageing, moisture, partial discharge in oil-impregnated paper (OIP) bushings | None for the bushing’s own mineral oil | Bushing fire, burning debris, ignition of surroundings | Dry bushings (RIP/RIS), bushing monitoring, condition-based replacement |
| Cable box or termination failure | Poor jointing, overheating, compound- or oil-filled boxes | Depends on the filling of the box | Fire in the cable box, fire spreading along cables | Air-insulated or plug-in terminations, cable fire stopping |
| On-load tap changer | Contact wear, arcing in the diverter compartment | Only if the tap changer compartment also contains the K-class liquid | Tap changer fire or rupture | Vacuum-type tap changer, same K-class liquid, monitoring |
| External fire exposure | Fire in adjacent equipment, cables or vehicles | Much more heat is needed to reach the fire point | Long, intense exposure can heat the liquid; tank may fail from pressure | Clearances, fire walls, water spray or sprinklers, limiting nearby fire loads |
| Leak and ignition | Gasket failure, mechanical damage | Small sources are unlikely to ignite a pool | Contaminated area; ignition if heated by another fire | Containment, inspection, drainage design |
| Mixed or contaminated liquid | Retrofill residues, top-up with the wrong fluid | Fire point of the mixture is lower | Transformer may no longer be K-class | Fire point check after retrofill or top-up, clear labelling |
| Solid insulation and other combustibles | Cellulose, wood, plastics, cable insulation | None | Additional fire load in a fully developed fire | Compartmentation, suppression |
| Smoke and combustion gases | Any fire | Esters contain no halogens, so no halogen acid gases form | Smoke, carbon monoxide and soot, especially in enclosed spaces | Detection, smoke control, protected escape routes |
| Firefighting near live equipment | Energised equipment during a fire | None | Electric shock, re-ignition | Disconnection and earthing procedures, signage, training |
| Firewater and environmental release | Spills, contaminated firewater | Biodegradability does not remove containment obligations | Contamination of soil, drains or water | Bund for liquid volume plus firewater and rain, separator suitable for esters |
Why sprays are the key residual risk
Released under pressure, a liquid breaks up into droplets. A fine mist can ignite at temperatures far below the flash point of the bulk liquid. A research review for the UK Health and Safety Executive notes that fine sprays of heavy oils with flash points above 300 °C can still ignite. During an internal fault, the arc is a strong ignition source right at the release point.
What changes with esters is what happens next. In published spray tests at 2 bar, a mineral oil mist kept burning for up to 49 seconds after the flame was removed, while a synthetic ester mist went out within at most 7 seconds. In practice this means: clear the arc fast, prevent the tank from rupturing, and make sure released liquid cannot reach other ignition sources. More: tank rupture and internal arc faults.
The component trap: bushings and cable boxes
Statistics compiled by the convener of the CIGRE working group on transformer fire safety attribute 70–80 % of transformer fires below 300 kV to bushings and cable boxes. An ester-filled transformer with oil-impregnated paper (OIP) bushings still carries mineral oil in each of these bushings – right at the most frequent failure point. Specifying dry bushings and suitable cable terminations is often the single most effective step after choosing the fluid. More: bushings, tap changers and cable boxes.
A bow-tie view
A bow-tie diagram is a clear way to present these risks. The central event is loss of containment of insulating liquid.
- Threats (left): internal arc, bushing failure, tap changer failure, mechanical damage, external fire.
- Preventive barriers: design and testing, condition monitoring (dissolved gas analysis, bushing monitoring), fast protection, tank strength and pressure relief.
- Mitigating barriers (right): K-class fluid, containment and flame traps, fire-rated separation, detection and suppression, smoke control.
- Consequences: fire, smoke, damage to adjacent assets, loss of supply, environmental release.
Data to request from the fluid supplier
- Flash point and fire point, with the test method (ISO 2592 / ASTM D92, Cleveland open cup)
- IEC 61039 class including the calorific value digit (e.g. K2, K3)
- Certification or listing, if required (FM Approvals Class 6933, listing for NEC 450.23)
- Safety data sheet with combustion products and extinguishing media
- Effect of mineral oil contamination on the fire point
- Density, for fire load and containment calculations
Arguing that residual risk is as low as reasonably practicable
In the UK, risks must be reduced “as low as reasonably practicable” (ALARP). For transformers, a typical line of argument follows the hierarchy of controls: avoid the hazard (location), substitute (K-class fluid or dry-type), engineer it out (protection, tank, dry bushings, containment, fire-rated separation), then manage what remains (monitoring, maintenance, emergency procedures). A measure can only be rejected if its cost is grossly disproportionate to the risk reduction it brings. More: transformer fire risk assessment.
Frequently asked questions
What is the main residual fire risk of an ester-filled transformer?
A high-energy internal arc that ruptures the tank and releases liquid as a spray while the arc is still burning. Fast protection, pressure relief and tank strength are the main controls.
Can an ester mist ignite?
Yes. Fine sprays of high-flash-point liquids can ignite when an ignition source is present. In published tests, ester mists went out quickly once the flame was removed, unlike mineral oil mists.
Do bushings contain mineral oil in an ester-filled transformer?
Oil-impregnated paper (OIP) bushings have their own sealed mineral oil filling. Resin-impregnated (RIP/RIS) bushings are dry alternatives.
Do esters produce toxic smoke?
Any burning organic material produces smoke, carbon monoxide and soot. Esters consist of carbon, hydrogen and oxygen, so no halogen acid gases are formed.
Related articles
- Fire Safety of Ester-Filled Transformers
- Transformer Tank Rupture and Internal Arc Faults
- Bushings, Tap Changers and Cable Boxes as Fire Sources
- Transformer Fire Risk Assessment: Method and Checklist
Sources and further reading
- Petersen, A.: Risk Equals Probability Times Consequences – T&D World (2014)
- HSE Research Report RR980: Generation of flammable mists from high flashpoint fluids (2013)
- Reid, J.: The Use of Ester based Transformer Liquids for Reduced Fire Risk and Lower Costs – IChemE Hazards 31 (2021)
- IEEE C57.156-2016: Guide for Tank Rupture Mitigation of Liquid-Immersed Power Transformers and Reactors
- FM Approvals Class 3990: Examination Standard for Liquid-Insulated Transformers (2022)
- HSE: ALARP at a glance
- CIGRE Technical Brochure 537: Guide for Transformer Fire Safety Practices (2013)
Need fire data for your risk register?
We provide fire-relevant data for our ester fluids and discuss scenarios with your fire engineering team. IsoTec products are supplied to customers outside Germany.