Transformer Fire Safety Glossary
The key terms of transformer fire safety – for fire engineers, specifiers and asset owners.
Updated 12 November 2026 · Published by IsoTec
Terms A–Z
- ALARP
- “As low as reasonably practicable”: UK principle that risks must be reduced unless the cost of further measures is grossly disproportionate to the benefit.
- Arc fault (internal arc)
- Electrical discharge inside the transformer after insulation failure; decomposes the liquid into gas and causes a rapid pressure rise.
- Auto-ignition temperature
- Temperature at which a liquid ignites in air without an ignition source, e.g. on a hot surface.
- Bow-tie analysis
- Risk method that shows the threats leading to a central event and the consequences that follow, with barriers on both sides.
- Buchholz relay
- Gas and oil-surge relay between tank and conservator that detects gas generation and liquid movement during internal faults.
- Bund
- Containment around or below a transformer that retains leaked liquid and firewater.
- Cable box
- Enclosure in which cables are connected to the transformer; may be air-insulated, compound-filled or oil-filled.
- Cleveland open cup
- Test method (ISO 2592 / ASTM D92) for flash point and fire point; basis of the IEC 61039 classification and FM Approvals Class 6933.
- Current-limiting fuse
- Fuse that interrupts high fault currents before they reach their peak, limiting the arc energy.
- Dissolved gas analysis (DGA)
- Analysis of gases dissolved in the insulating liquid; detects developing faults such as overheating and discharges.
- Dry-type transformer
- Transformer without insulating liquid, usually with cast-resin windings.
- EI / REI
- Fire resistance ratings: integrity (E), insulation (I) and, for load-bearing elements, resistance (R), followed by minutes – e.g. EI 60.
- Enhanced protection
- Term in IEC 61936-1: tank rupture strength, pressure relief and protection against low- and high-current faults.
- F0 / F1
- Fire behaviour classes of dry-type transformers (IEC 60076-11). F1 applies where there is a fire hazard and requires restricted flammability.
- Fire load
- Total heat that can be released by burning materials; for the liquid: mass × net calorific value.
- Fire point
- Lowest temperature at which a liquid keeps burning for at least 5 seconds after ignition.
- Flame trap
- Layer of gravel or crushed rock over a sump that extinguishes burning liquid draining through it.
- Flash point
- Lowest temperature at which the vapours of a liquid ignite briefly when an ignition source is applied.
- FM Approved
- Certified by FM Approvals – for transformer fluids under Class 6933, for transformers under Class 3990.
- Heat release rate
- Rate at which a fire releases energy, in kW or MW; determines fire size and smoke production.
- IEC 61039
- Standard classifying insulating liquids by fire point (O, K, L) and net calorific value (1, 2, 3).
- K-class
- Insulating liquid with a fire point above 300 °C according to IEC 61039.
- Less-flammable liquid
- Term used by the NEC and FM Global for insulating liquids with a fire point of at least 300 °C that are listed or certified.
- Mist ignition
- Ignition of a fine spray of liquid; can occur well below the flash point of the bulk liquid if an ignition source is present.
- Natural ester
- Insulating liquid based on refined vegetable oils; typically class K2.
- Net calorific value
- Heat released by complete combustion, without the condensation heat of water; used for the IEC 61039 digit.
- OIP bushing
- Oil-impregnated paper bushing; contains its own mineral oil filling.
- On-load tap changer (OLTC)
- Device that changes the transformer ratio under load; conventional types switch in liquid, vacuum types in vacuum interrupters.
- Pool fire
- Fire burning on the surface of a pool of liquid; requires the liquid surface to reach its fire point.
- Pressure relief device
- Valve that opens at a set pressure to limit tank pressure during internal faults.
- Retrofilling
- Replacing the mineral oil of an existing transformer with another liquid, e.g. an ester.
- RIP / RIS bushing
- Resin-impregnated paper or resin-impregnated synthetic bushing; dry design without free oil.
- Sudden pressure relay
- Relay that trips the transformer on a rapid rise of tank pressure.
- Synthetic ester
- Insulating liquid made from polyols and fatty acids; typically class K3.
- Tank rupture
- Failure of the transformer tank, cover or turret under the pressure of an internal arc.
- Water mist
- Fire suppression with fine water droplets; one of the options for indoor transformer protection.