Transformer Fire Safety Glossary

The key terms of transformer fire safety – for fire engineers, specifiers and asset owners.

Updated 12 November 2026 · Published by IsoTec

Terms A–Z

ALARP
“As low as reasonably practicable”: UK principle that risks must be reduced unless the cost of further measures is grossly disproportionate to the benefit.
Arc fault (internal arc)
Electrical discharge inside the transformer after insulation failure; decomposes the liquid into gas and causes a rapid pressure rise.
Auto-ignition temperature
Temperature at which a liquid ignites in air without an ignition source, e.g. on a hot surface.
Bow-tie analysis
Risk method that shows the threats leading to a central event and the consequences that follow, with barriers on both sides.
Buchholz relay
Gas and oil-surge relay between tank and conservator that detects gas generation and liquid movement during internal faults.
Bund
Containment around or below a transformer that retains leaked liquid and firewater.
Cable box
Enclosure in which cables are connected to the transformer; may be air-insulated, compound-filled or oil-filled.
Cleveland open cup
Test method (ISO 2592 / ASTM D92) for flash point and fire point; basis of the IEC 61039 classification and FM Approvals Class 6933.
Current-limiting fuse
Fuse that interrupts high fault currents before they reach their peak, limiting the arc energy.
Dissolved gas analysis (DGA)
Analysis of gases dissolved in the insulating liquid; detects developing faults such as overheating and discharges.
Dry-type transformer
Transformer without insulating liquid, usually with cast-resin windings.
EI / REI
Fire resistance ratings: integrity (E), insulation (I) and, for load-bearing elements, resistance (R), followed by minutes – e.g. EI 60.
Enhanced protection
Term in IEC 61936-1: tank rupture strength, pressure relief and protection against low- and high-current faults.
F0 / F1
Fire behaviour classes of dry-type transformers (IEC 60076-11). F1 applies where there is a fire hazard and requires restricted flammability.
Fire load
Total heat that can be released by burning materials; for the liquid: mass × net calorific value.
Fire point
Lowest temperature at which a liquid keeps burning for at least 5 seconds after ignition.
Flame trap
Layer of gravel or crushed rock over a sump that extinguishes burning liquid draining through it.
Flash point
Lowest temperature at which the vapours of a liquid ignite briefly when an ignition source is applied.
FM Approved
Certified by FM Approvals – for transformer fluids under Class 6933, for transformers under Class 3990.
Heat release rate
Rate at which a fire releases energy, in kW or MW; determines fire size and smoke production.
IEC 61039
Standard classifying insulating liquids by fire point (O, K, L) and net calorific value (1, 2, 3).
K-class
Insulating liquid with a fire point above 300 °C according to IEC 61039.
Less-flammable liquid
Term used by the NEC and FM Global for insulating liquids with a fire point of at least 300 °C that are listed or certified.
Mist ignition
Ignition of a fine spray of liquid; can occur well below the flash point of the bulk liquid if an ignition source is present.
Natural ester
Insulating liquid based on refined vegetable oils; typically class K2.
Net calorific value
Heat released by complete combustion, without the condensation heat of water; used for the IEC 61039 digit.
OIP bushing
Oil-impregnated paper bushing; contains its own mineral oil filling.
On-load tap changer (OLTC)
Device that changes the transformer ratio under load; conventional types switch in liquid, vacuum types in vacuum interrupters.
Pool fire
Fire burning on the surface of a pool of liquid; requires the liquid surface to reach its fire point.
Pressure relief device
Valve that opens at a set pressure to limit tank pressure during internal faults.
Retrofilling
Replacing the mineral oil of an existing transformer with another liquid, e.g. an ester.
RIP / RIS bushing
Resin-impregnated paper or resin-impregnated synthetic bushing; dry design without free oil.
Sudden pressure relay
Relay that trips the transformer on a rapid rise of tank pressure.
Synthetic ester
Insulating liquid made from polyols and fatty acids; typically class K3.
Tank rupture
Failure of the transformer tank, cover or turret under the pressure of an internal arc.
Water mist
Fire suppression with fine water droplets; one of the options for indoor transformer protection.